Residual Current Circuit Breaker Acti9 4Poles A-Type 40A 30mA 415V IP20 Schneider Electric
This Acti9 iID is a standard-fitted and reliable double-ended 4Poles, TypeA, 40A residual current circuit breaker.
Watch this product and we will notify you once it is back in stock.
Residual Current Circuit Breaker Acti9 4Poles A-Type 40A 30mA 415V IP20 Schneider Electric
Description
This Acti9 iID is a standard-fitted and reliable double-ended residual current circuit breaker (RCCB). It is a 4P circuit breaker with a rated current of 40A, a sensitivity of 30mA with a protection class of type A. This product protects against electric shocks through direct or indirect contact and against fire hazards. It has the function of disconnecting electrical circuits in the event of an earth fault. Its unique Visitrip indicator reduces troubleshooting time by displaying a red mechanical indicator on the front if it trips due to an earth fault. This product also has a VisiSafe window with a green strip on the rocker indicating full opening of the circuit, allowing downstream maintenance. This product complies with the EN/IEC 61008-1 standard. The (Im/IΔm) rated breaking and short-circuit capacity is 1500A. The (Inc/IΔc) conditional short-circuit current rating is 10kA. The mechanical endurance is up to 20,000 cycles and the electrical endurance is up to 15,000 cycles. The Ue operating voltage is 380VAC to 415VAC. The Ui rated voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is intended for mounting on a DIN rail. It has a degree of protection IP20 (according to IEC/EN 60529 standard) and IP40 mounted in a modular enclosure. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 85°C.
Technical Information
- Number of poles: 4P
- Neutral conductor placement: Left
- Rated current [In]: 40 A
- Rated voltage [Ue]: 380-415 V AC 50/60 Hz
- Type of network: AC
- Leakage current sensitivity: 30 mA
- Earth fault protection with time delay: Instantaneous
- Earth leakage circuit breaker class: Type A
- Current tripping technology: Voltage independent
- Rated current breaking and final capacity: Idm 1500 A, Im 1500 A
- Specified short-circuit current: 10 kA
- Insulation voltage [Ui]: 500 V AC 50/60 Hz
- Impulse withstand voltage [Uimp]: 6 kV
- Position indication: Yes
- Operation type: Rocker
- Assembly method: Clip-on
- Mounting brackets: DIN rail
- 9 mm module: 8
- Mechanical life: 20,000 cycles
- Electrical life: 15,000 cycles AC-1
- Description of locking options: Padlocking device
- Cable scale length: 14 mm for top or bottom connection
- Tightening torque: 3.5 Nm (top or bottom)
- IP protection class: IP20 conforming to IEC 60529
- Pollution level: 3
- Electromagnetic compatibility: Impulse withstand 8/20 µs, 250 A conforming to EN/IEC 61008-1
- Ambient temperature during operation: −25…60 °C
- Ambient air temperature for storage: −40…85 °C
Specification
- Colour: White
- Material: Plastic
- Surface protection: None
- Surface finishing: None
- Measure (WxHxD): 72×91×73 mm