Miniature Circuit Breaker Screw Connection 2Poles B-Characteristic 40A 10kA 400V IP20 Hager
Mini circuit breaker (formerly miniature circuit breaker) 2-pole with screw connection NBN240 40A, B-characteristic with a breaking capacity of 10kA.
Watch this product and we will notify you once it is back in stock.
Miniature Circuit Breaker Screw Connection 2Poles B-Characteristic 40A 10kA 400V IP20 Hager
Description
Mini circuit breaker (formerly miniature circuit breaker) 2-pole with screw connection NBN240 40A, B-characteristic with a breaking capacity of 10kA. Double connection for power supply, one for phase busbar and one for cables. This provides a safe connection. Provides reliable and safe protection of cables/lines against overload and short circuit. MCB (Mini Circuit Breaker) is referred to in older regulations as miniature circuit breaker/automatic fuse.
Specifications
- Rated current: 40 A
- Operating breaking capacity Ics under 230 V AC according to IEC 60947-2: 15 kA
- Rated short-circuit breaking capacity Icn under 230 V AC according to IEC 60898-1: 10 kA
- Ultimate short-circuit breaking capacity Icu under 230 V AC IEC 60947-2: 30 kA
- Ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-2: 15 kA
- Rated current -25°C: 60.16 A
- Rated current at -20°C: 58.43 A
- Rated current -15°C: 56.70 A
- Rated current -10°C: 55.35 A
- Rated current -5°C: 53.24 A
- Rated current at 0°C: 51.51A
- Rated current 5°C: 49.78 A
- Rated current 10°C: 48.06 A
- Rated current 15°C: 46.33 A
- Rated current at 20°C: 44.60 A
- Rated current 25°C: 42.87 A
- Rated current 30°C: 40 A
- Rated current 35°C: 39.41 A
- Rated current at 40°C: 37.69 A
- Rated current at 45°C: 35.96 A
- Rated current at 50°C: 34.99 A
- Rated current 55°C: 32.50 A
- Rated current 60°C: 30.77 A
- Rated current 65°C: 29.04 A
- Rated current 70°C: 27.31 A
- Number of poles: 2P
- Curve: B
- Number of modules: 2
- Rated short-circuit breaking capacity Icn (IEC 60898-1): 10 kA
- Nominal tightening torque upper connection: 2.80 - 2.80 Nm
- Nominal tightening torque lower connection: 2.80 - 2.80 Nm
- Nominal tightening torque: 2.80 - 2.80 Nm
- Type of lower connection on standard components: BIConnect
- Type of upper connection on standard components: Screw connection
- 360 degree mounting position possible: Yes
- Rated operational voltage Ue: 400 - 400 V
- Supply voltage: AC
- Rated insulation voltage Ui: 500 V
- Rated impulse withstand voltage Uimp: 6000 V
- Frequency: 50 - 60 Hz
- Connection area input and output with screws, solid conductor: 1 - 35 mm²
- Connection area input and output with screws, flexible conductor: 1 - 25 mm²
- Connection area at input with screw, with flexible conductor: 1 - 25 mm²
- Connection type: Screw terminal
- Top connection for standard components: Adapted terminal block
- Downward connection for standard components: Adapted terminal block
- Protection class (IP): IP20
- Pollution degree according to IEC 60664 / IEC 60947-2: 2
- Energy limitation class I²t: 3
- Operating temperature: -25 - 70 °C
- Total power loss at nominal rated current: 6.70 W
- Mechanical service life (electrical switching operations): 4000
- Mechanical service life (switching operations): 20000
- Height: 83 mm
- Width: 35 mm
- Depth: 70 mm