Personal Protection Circuit Breaker QuickConnect 1Pole+Neutral B-Characteristic Type-A 10A 6kA 30mA 240V IP2X Hager
Combination of earth leakage circuit breaker and miniature circuit breaker that protects against overcurrent, overheating/fire and electrical faults.
Watch this product and we will notify you once it is back in stock.
Personal Protection Circuit Breaker QuickConnect 1Pole+Neutral B-Characteristic Type-A 10A 6kA 30mA 240V IP2X Hager
Description
Personal protection circuit breaker with quick connection QuickConnect ADS910D also called personal protection circuit breaker is a combination of earth leakage circuit breaker and miniature circuit breaker that prevents and protects against e.g. overcurrent, overheating/fire and electrical faults that can lead to personal injury. The personal protection circuit breaker is 10A with B-characteristic and has a breaking capacity of 6kA and a fault current of 30mA. It has a 1-pole thermal protection with a 2-pole break.
Specifications
- Number of poles: 1P+N
- Curve: B
- Number of poles: 2
- Rated current: 10 A
- Rated fault current Idn: 30 mA
- Rated current -25°C: 12 A
- Rated current at -20°C: 11.80 A
- Rated current -15°C: 11.70 A
- Rated current -10°C: 11.50 A
- Rated current -5°C: 11.30 A
- Rated current at 0°C: 11.10 A
- Rated current 5°C: 11 A
- Rated current 10°C: 10.80 A
- Rated current 15°C: 10.60 A
- Rated current at 20°C: 10.40 A
- Rated current 25°C: 10.20 A
- Rated current 30°C: 10 A
- Rated current 35°C: 9.90 A
- Rated current at 40°C: 9.70 A
- Rated current at 50°C: 9.40 A
- Rated current 55°C: 9.30 A
- Rated current 60°C: 9.10 A
- Correction factor for 2 and more miniature circuit breakers mounted next to each other: 1
- Correction factor for 3 and more miniature circuit breakers mounted next to each other: 0.95
- Correction factor for 4 and 5 miniature circuit breakers mounted next to each other: 0.90
- Correction factor for 6 and more miniature circuit breakers mounted next to each other: 0.85
- Min./Max. thermal trip threshold in AC operation: 1.13 - 1.45 A
- Rated short-circuit breaking capacity Icn below 230 V AC according to IEC 60898-1: 6 kA
- Rated short-circuit breaking capacity Icn (IEC 60898-1): 6 kA
- Leakage current type: A
- Protection class (IP): IP2X
- Rated insulation voltage Ui: 500 V
- Rated impulse withstand voltage Uimp: 4000 V
- Max. operating voltage (Umax): 240 V
- Rated operating voltage Ue: 240 - 240 V
- Overvoltage category according to IEC 60947-1: 3
- Total power loss at nominal rated current: 3.40 W
- Frequency: 50 - 50 Hz
- Operating conditions:
- Max. altitude: 2000 m
- Energy limitation class I²t: 3
- Operating temperature: -25 - 40 °C
- Storage/transport temperature: -25 - 70 °C
- Mechanical service life (electrical switching): 2000
- Mechanical service life (switching): 2000
- Connection type: Quickconnect
- Connection area at incoming with screw, with flexible conductor: 1.5 - 4.0 mm²
- Connection area input and output with screws, solid conductor: 1.5 - 4.0 mm²
- Connection area at outgoing with screw, with flexible conductor: 1 - 16 mm²
- Connection area at outgoing with screw, solid conductor: 1 - 25 mm²
- Nominal tightening torque: 2.1 - 2.1 Nm
- Type of upper connection on standard components: Quickconnect
- Type of lower connection on standard components: BIConnect, Phase busbar Quickconnect
- Number of modules: 2
- Height: 94 mm
- Width: 35 mm
- Depth: 68 mm
- Fits DIN rail: Yes