Personal Protection Circuit Breaker QuickConnect 1Pole+Neutral B-Characteristic Type-A 16A 10kA 30mA 240V IP2X Hager
Combination of earth leakage circuit breaker and miniature circuit breaker that protects against overcurrent, overheating/fire and electrical faults.
Watch this product and we will notify you once it is back in stock.
Personal Protection Circuit Breaker QuickConnect 1Pole+Neutral B-Characteristic Type-A 16A 10kA 30mA 240V IP2X Hager
Description
Personal protection circuit breaker ADA516D also called personal protection circuit breaker is a combination of earth leakage circuit breaker and miniature circuit breaker that prevents and protects against e.g. overcurrent, overheating/fire and electrical faults that can lead to personal injury. The personal protection circuit breaker is 16A with B-characteristic and has a breaking capacity of 10kA and a fault current of 30mA. It has a 1-pole thermal protection with a 2-pole break. An all-pole and safe break in the event of: Ground fault current in the system, Overload, Short circuit.
Specifications
- Number of poles: 1P+N
- Curve: B
- Number of poles: 2
- Leakage current type: A
- Protection class (IP): IP2X
- Rated short-circuit breaking capacity Icn (IEC 60898-1): 10 kA
- Rated insulation voltage Ui: 500 V
- Rated impulse withstand voltage Uimp: 4000 V
- Max. operating voltage (Umax): 240 V
- Rated operating voltage Ue: 240 - 240 V
- Overvoltage category according to IEC 60947-1: 3
- Supply voltage: AC
- Rated current: 16 A
- Rated residual current Idn: 30 mA
- Rated current -25°C: 18.50 A
- Rated current at -20°C: 18.30 A
- Rated current -15°C: 18.10 A
- Rated current -10°C: 17.90 A
- Rated current -5°C: 17.70 A
- Rated current at 0°C: 17.40 A
- Rated current 5°C: 17.20 A
- Rated current 10°C: 17 A
- Rated current 15°C: 16.70 A
- Rated current at 20°C: 16.50 A
- Rated current 25°C: 16.20 A
- Rated current 30°C: 16 A
- Rated current 35°C: 15.80 A
- Rated current at 40°C: 15.60 A
- Rated current at 45°C: 15.40 A
- Rated current at 50°C: 15.20 A
- Rated current 55°C: 15 A
- Rated current 60°C: 14.80 A
- Correction factor for 2 and more miniature circuit breakers mounted next to each other: 1
- Min./Max. thermal tripping threshold in AC operation: 1.13 - 1.45 A
- Correction factor for 3 and more miniature circuit breakers mounted next to each other: 0.95
- Correction factor for 4 and 5 miniature circuit breakers mounted next to each other: 0.90
- Correction factor for 6 and more miniature circuit breakers mounted next to each other: 0.85
- Rated short-circuit breaking capacity Icn under 230 V AC according to IEC 60898-1: 10 kA
- Operating breaking capacity Ics AC according to IEC 60898-1: 7.50 kA
- Total power loss at nominal rated current: 5.20 W
- Frequency: 50 - 50 Hz
- Max. altitude: 2000 m
- Energy limitation class I²t: 3
- Operating temperature: -25 - 40 °C
- Storage/transport temperature: -25 - 70 °C
- Pollution degree according to IEC 60664 / IEC 60947-2: 2
- Moisture protection: For all climates
- Nominal tightening torque lower connection: 2.10 - 2.10 Nm
- Nominal tightening torque upper connection: 2.10 - 2.10 Nm
- Nominal tightening torque: 2.10 - 2.10 Nm
- Type of upper connection on standard components: Screw connection
- Type of lower connection on standard components: BIConnect
- Mechanical service life (electrical switching): 2000
- Mechanical service life (switching): 2000
- Connection type: Screw terminal
- Area flexible conductor: 1 - 16 mm²
- Area solid conductor: 1 - 25 mm²
- Connection area for incoming with screw, with flexible conductor: 1 - 16 mm²
- Connection area input and output with screws, solid conductor: 1 - 25 mm²
- Connection area input and output with screws, flexible conductor: 1 - 16 mm²
- Connection area input and output with screws, solid conductor: 1 - 25 mm²
- Number of modules: 2
- Height: 83 mm
- Width: 35 mm
- Depth: 68 mm
- Fits DIN rail: Yes